Breaker Size Calculator

Find the smallest standard breaker for a load, sized at 125% for continuous loads (3 hours or more).

What Do You Want to Find?
Values from the equipment nameplate.
Breaker size
Load current
Minimum rating
Wire check
Standard sizes nearby
Work

Saved Calculations

Items you add are saved in this browser.

NameCalculationResultRemove

How to Size a Breaker

Minimum rating = non-continuous load + 125% × continuous load (NEC 210.20(A), 215.3)
Amps = watts ÷ volts (single-phase)   watts ÷ (volts × √3) (three-phase)

Round up to the next standard rating in NEC 240.6(A): 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A and up.

Worked Example

Tips

Motors, HVAC equipment and appliances with nameplate "maximum overcurrent protection" follow their own rules; use the nameplate. Have a licensed electrician confirm sizing and wiring against your local code.