Electrical Box Fill Calculator
Count the wires, devices and fittings in a box and check it against the box’s cubic-inch rating.
–
Required volume
- Volume allowances
- Per-conductor volume
- Box volume
- Room left
- Work
Saved Calculations
Items you add are saved in this browser.
| Name | Calculation | Result | Remove |
|---|
NEC Box Fill Rules (314.16(B))
| Wire size | Volume per conductor |
|---|---|
| 18 AWG | 1.50 in³ |
| 16 AWG | 1.75 in³ |
| 14 AWG | 2.00 in³ |
| 12 AWG | 2.25 in³ |
| 10 AWG | 2.50 in³ |
| 8 AWG | 3.00 in³ |
| 6 AWG | 5.00 in³ |
Each insulated conductor entering the box counts once. Each device (switch or receptacle) counts twice, based on the largest wire connected to it. All internal cable clamps together count once; all equipment grounding conductors together count once (plus one more for an isolated ground set); each fixture stud or hickey counts once.
Worked Example
Tips
This page uses one wire size for everything (the largest), which is conservative when sizes are mixed. Check the local code in force (NEC 2023 in many areas) and have work inspected.